PCS-985U Voltage Injector
  • The stator earth fault protection with external voltage injector can detect 100% earth faults in the stator windings of generator which is connected with the network via a unit transformer. The auxiliary power supply device PCS-985U can inject low-frequency external power source to the generator stator winding side, PCS-985U coordinate with PCS-985, then one set of integral generator stator ground fault protection with 20Hz voltage injection is formed.

    The hardware of the PCS-985U is constituted by low-frequency power source, low-frequency filter, converter, voltage-divide resistance and etc. The dimensions of PCS-985U is 266×482.6×281mm (height×width×depth), it can be installed on the spot or in the relay room. PCS-985U has high flexibility and reliability.

    Generator neutral point is grounding via a grounding transformer. Through the voltage divider, the PCS-985 protection relay can get UG0. In addition, IG0 is measured via a miniature CT. If a ground fault happens at the generator stator winding, generally the injected low-frequency voltage will decrease and the low-frequency current will increase. If the ground fault location is not near to the neutral point, the zero-sequence current will increase significantly.

  • log on
    phone:
    password:
    Code:
    Register
    Register
    phone:
    password:
    E-mail:
    company:
    name:
    country:
    Code:
    Previous:PCS-985TE Transformer Relay Next:PCS-985RE Rotor Earth-Fault Relay Back to list

    © Copyright NR Electric Co., Ltd.
    All Rights Reserved.

    About us Service & Support Company Training Contact Us

    Solutions Power Generation Transmission System Distribution Network Industrial Consumer

    Products Protection,Automation&Control FACTS HVDC Renewable & Microgrid