PCS-SCD Configuration Tool
  • PCS-SCD Configuration Tool is developed for the engineering implementation of IEC61850. It is the visual configuration tool used to set SCL files, including creating, editing and viewing SCL files that conform to IEC61850-6 regulations. Users can construct the substation configuration, structures and models via this tool, and quickly design and manage substation settings.

  • Functions Advanced Operations Configure SCL Files
    • Create the substation configuration description (SCD) file in accordance with IEC61850-6 regulations.

    • Build a single line diagram for the primary system of the substation.

    • Manage the version of SCD files.

    • Construct different substation structures and create the complete system specification description (SSD).

    • Import the IED into the ICD that conforms to IEC61850-6.

    • Associate different intelligent electronic devices and logical nodes (LN) to substation details, and complete the configuration of the substation system according to IEC61850-6.

    • Edit and maintain the functions and date elements in IED.

    • Define the substation communication configuration.

    • Check the data templates and solve the conflicts.

    • Verify standard SCL Schema.

    • Provide grammar and semantic check.

    • Using the Filter in IED Selector

    The IED Selection Window provides the data sources which are acquired from IED during the process of SCL configuration. Considering the IED selector needs a large quantity of data, a filter is provided for data locating.

    • Batch Export CID Files

    Select Batch Export CID Files from the Tool to open Batch Export CID Files dialog box. The PCS-SCD tool can export CID files of all IEDs in the current SCL file.

    • Batch Export UAPC-GOOSE Files

    Select Batch Export uapc-goose Files from the Tool to open Batch Export uapc-goose Files dialog box. The PCS-SCD tool supports the batch export of all uapc-goose files, and the dialog box lists all IEDs in the current SCL file.

    • Batch Export CID and UAPC-GOOSE Files

    The PCS-SCD tool supports the batch export of all CID and uapc-goose files, and the dialog box lists all IEDs in the current SCL file.

    • Batch Export Terminal Map

    The PCS-SCD tool supports the batch export of all terminal map files in Excel format, and the dialog box lists all IEDs in the current SCL file.

    • Batch Export CIM XML

    The PCS-SCD tool supports the batch export of IEC61970 CIM XML files in Excel format, and the dialog box lists all IEDs in the current SCL file.

    • Schema Validation

    Select Schema Validation in the Tool menu to start the schema validation of current SCL file. The validation results will be shown in the Validation Output Window.

    • Semantic Validation

    The PCS-SCD tool supports the validation of the Communication and all IEDs in the current SCL file according to the following rules.

     Communication Validation Contents:

      Validity of ConnectedAP’s quoting the IED and AccessPoint

      Validity and uniqueness of MMS Web’s IP Address

      Validity of GSE’s quoting the GSEControl

      Validity and uniqueness of GSE APPID

      Validity of SMV’s quoting the SampledValueControl

     IED Validation Contents:

      Validity of object instances (DOI, SDI, DAI) under the LN quoting the DataTypeTemplate

      Validity and uniqueness of GSEControl appID

      Uniqueness of DataSet FCDA (If there is repetition, FCDA will send off the warning)

      Validity of DataSet FCDA quoting its internal signal

      Validity of Inputs quoting its internal and external signals

    • Header Configuration

    Click Header in the SCL browser window, the Header configuration window is popped up.

    The Header configuration window displays the configuration of changed information lists in the SCL file, and provides operations such as New, Delete, Move Up and Move Down for changed information.

    • Communication Configuration

    Click Communication in the SCL browser window, the communication configuration window is shown.

    The communication configuration window provides the configuration of SubNetwork lists in the SCL file, and provides operations such as New, Delete, Move Up and Move Down for each SubNetwork.

    • Subnetwork Configuration

    Click one SubNetwork under Communication in the SCL browser window to open subnetwork configuration window. The SubNetwork configuration window provides the configuration of ConnectedAP, Address, GSE and SMV under one SubNetwork in the SCL file.

    • IED List Configuration

    Click IED in the SCL browser window to open IED list configuration window.

    The IED List Configuration Window provides the management and configuration of all IEDs in the SCL file, such as create, update and delete an IED, adjust the position of one certain IED in the SCL file and edit the attributes of an IED.

    • IED Configuration

    Under the IED configuration window, users can configure a certain IED in the SCL file. Including:

    Logic Node Configuration

    Data Set Configuration

    GSE Control Configuration

    SMV Control Configuration

    Inputs Configuration

    Report Control Configuration

    Substation List Configuration

    Click the Substation in the SCL Browser Window, and the Substation List Configuration Window is open.

    The Substation List Configuration Window provides the configuration of Substation lists in the SCL file as well as operations for one certain Substation, i.e., New, Delete, Move Up and Move Down. All cells in the configuration window are editable.

    • Substation Configuration

    The Substation Configuration Window provides the specific configuration of one certain Substation in the SCL file. The Substation Configuration Window is opened by clicking one specific Substation under the Substation in the SCL Browser Window.

    The PCS-SCD tool supports the construction of single line diagram for primary system of the substation in the graphical form, automatically generates the Substation model which conforms to the definition in IEC61850-6 according to the single line diagram, sets the association of the Substation model with the logical node of IED, etc.

    log on
    phone:
    password:
    Code:
    Register
    Register
    phone:
    password:
    E-mail:
    company:
    name:
    country:
    Code:
    Previous:PCS-Explorer IED Configuration & Debugging Tool Next:PCS-COMM Configuration & Debugging Tool Back to list

    © Copyright NR Electric Co., Ltd.
    All Rights Reserved.

    About us Service & Support Company Training Contact Us

    Solutions Power Generation Transmission System Distribution Network Industrial Consumer

    Products Protection,Automation&Control FACTS HVDC Renewable & Microgrid